Instrument Loop Troubleshooting Cheat Sheet
A one page fault finding guide for instrument loops: what each symptom usually means, what to measure and the classic flow, level and valve faults.
One page A4Print ready PDFFree, no sign up
Download
A one page A4 sheet to print, pin up in the workshop or keep on your phone. Everything on it is also shown below.
Download PDF A4 · 57 KBLoop current symptoms
| Reading | Likely cause |
|---|---|
| 0 mA | Open loop, no supply, blown fuse |
| ≤ 3.6 mA | Transmitter fault, downscale burnout |
| ≥ 21 mA | Fault upscale, sensor break (TC) |
| Fixed value | Loop test or fixed current mode, manual DCS |
| Noisy | Grounding, shield, VFD noise, low damping |
| Offset | Zero shift, wrong range, wet leg, mounting |
What to measure
- Loop current in series or with a clamp meter.
- Supply voltage at the PSU.
- Voltage at transmitter terminals (≥ minimum on data sheet).
- Loop resistance with the loop open.
- Insulation to earth if earth fault alarms appear.
DP flow faults
| Symptom | Check |
|---|---|
| Reads low | Gas in liquid legs, HP leak, plugged HP tap |
| Reads high | LP leak, plugged LP tap, liquid in gas legs |
| Reads at zero flow | Missing low flow cutoff, equaliser open |
| Double square root | Root in transmitter and DCS |
Advertisement
Level faults
| Symptom | Check |
|---|---|
| DP level wrong | Density change, wet leg loss, seal damage |
| Radar jumps | False echoes, foam, buildup, mapping |
| Stuck full | Level in blocking distance, coating |
Temperature faults
| Symptom | Check |
|---|---|
| Reads ambient | Element not in well, air gap |
| Moves wrong way | TC polarity reversed |
| Offset few °C | Copper extension cable, CJC, 2 wire leads |
| Upscale | Open element or wire |
Control valve faults
| Symptom | Check |
|---|---|
| Does not move | Air supply, I/P or positioner, seized stem |
| Hunting | Stiction, positioner gain, loose feedback |
| Passing | Seat wear, bench set, thrust |
| Slow | Blocked vent, small solenoid, booster |
Method
- 1. Confirm the complaint with operations.
- 2. Check DCS: mode, alarms, scaling.
- 3. Measure current and voltage.
- 4. Split the loop: field or system side?
- 5. Check the process: taps, legs, valves.
- 6. Fix, test, document, inform.
Related Calculators and Tools
Advertisement
Frequently Asked Questions
How do I tell if the fault is in the field or the DCS?
Measure the loop current in the field and compare with the DCS reading; a match points to the process or transmitter.
What causes 21 mA on a temperature loop?
Often an open sensor with upscale burnout.
Why does a DP flow read low?
Gas trapped in liquid impulse lines, or a leak on the HP side, are common causes.
You May Also Like
Learn more on the blog
Instrumentation calibration and troubleshooting guide
A practical guide on instrumentationblog.in that explains the theory behind this cheat sheet.
Read Full ArticleMore Cheat Sheets
4 to 20 mA Cheat SheetPrintable A4 PDFFlow Measurement Formulas Cheat SheetPrintable A4 PDFPressure Cheat SheetPrintable A4 PDFTemperature Measurement Cheat SheetPrintable A4 PDFLevel Measurement Formulas Cheat SheetPrintable A4 PDFControl Valve Cheat SheetPrintable A4 PDFElectrical Formulas Cheat SheetPrintable A4 PDFOp Amp Formulas Cheat SheetPrintable A4 PDFElectronic Component Codes Cheat SheetPrintable A4 PDFPID Tuning Cheat SheetPrintable A4 PDFISA Instrument Letter Codes Cheat SheetPrintable A4 PDFIP, NEMA and Ex Rating Cheat SheetPrintable A4 PDFSIL and Functional Safety Cheat SheetPrintable A4 PDFCalibration and Uncertainty Cheat SheetPrintable A4 PDFAnalytical Instruments Cheat SheetPrintable A4 PDFModbus and HART Cheat SheetPrintable A4 PDFPt100 and Thermocouple Tables Cheat SheetPrintable A4 PDFPLC I/O and Signals Cheat SheetPrintable A4 PDFEngineering Units Conversion Cheat SheetPrintable A4 PDF