Pt100 and Thermocouple Tables Cheat Sheet
Quick reference values for field checks: thermocouple mV at key temperatures (NIST ITS-90 reference functions, 0 °C reference junction), Pt100 resistance and tolerances.
One page A4Print ready PDFFree, no sign up
Download
A one page A4 sheet to print, pin up in the workshop or keep on your phone. Everything on it is also shown below.
Download PDF A4 · 60 KBPt100 resistance (IEC 60751)
| °C | Ω |
|---|---|
| −50 | 80.31 |
| 0 | 100.00 |
| 25 | 109.73 |
| 50 | 119.40 |
| 100 | 138.51 |
| 150 | 157.33 |
| 200 | 175.86 |
| 250 | 194.10 |
| 300 | 212.05 |
| 400 | 247.09 |
| 500 | 280.98 |
Pt1000 = Pt100 values × 10.
Type K, J, T (mV)
| °C | −100 | 0 | 25 | 50 | 100 | 200 | 300 | 400 | 500 | 600 | 800 | 1000 | 1200 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| K | −3.554 | 0 | 1.000 | 2.023 | 4.096 | 8.138 | 12.209 | 16.397 | 20.644 | 24.905 | 33.275 | 41.276 | 48.838 |
| J | −4.633 | 0 | 1.277 | 2.585 | 5.269 | 10.779 | 16.327 | 21.848 | 27.393 | 33.102 | 45.494 | 57.953 | 69.553 |
| T | −3.379 | 0 | 0.992 | 2.036 | 4.279 | 9.288 | 14.862 | 20.872 |
Type N, E (mV)
| °C | −100 | 0 | 25 | 50 | 100 | 200 | 300 | 400 | 500 | 600 | 800 | 1000 | 1200 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| N | −2.407 | 0 | 0.659 | 1.340 | 2.774 | 5.913 | 9.341 | 12.974 | 16.748 | 20.613 | 28.455 | 36.256 | 43.846 |
| E | −5.237 | 0 | 1.495 | 3.048 | 6.319 | 13.421 | 21.036 | 28.946 | 37.005 | 45.093 | 61.017 | 76.373 |
Advertisement
Type R, S, B (mV)
| °C | 0 | 100 | 200 | 400 | 600 | 800 | 1000 | 1200 | 1400 | 1600 |
|---|---|---|---|---|---|---|---|---|---|---|
| R | 0 | 0.647 | 1.469 | 3.408 | 5.583 | 7.950 | 10.506 | 13.228 | 16.040 | 18.849 |
| S | 0 | 0.646 | 1.441 | 3.259 | 5.239 | 7.345 | 9.587 | 11.951 | 14.373 | 16.777 |
| B | 0 | 0.033 | 0.178 | 0.787 | 1.792 | 3.154 | 4.834 | 6.786 | 8.956 | 11.263 |
Cold junction check (example K)
- Measure mV at the terminals: 3.096 mV.
- Terminal temperature 25 °C → add 1.000 mV.
- Total 4.096 mV → 100 °C.
- Add mV, never °C.
Tolerances
| Sensor | Class | Tolerance |
|---|---|---|
| Pt100 | A | ± (0.15 + 0.002 |t|) °C |
| Pt100 | B | ± (0.3 + 0.005 |t|) °C |
| K, N | 1 | ± 1.5 °C or 0.4 % |t| |
| J | 1 | ± 1.5 °C or 0.4 % |t| |
| T | 1 | ± 0.5 °C or 0.4 % |t| |
Related Calculators and Tools
Advertisement
Frequently Asked Questions
Are these values exact?
They are calculated from the NIST ITS-90 reference functions to three decimals with a 0 °C reference junction.
Why is type B almost zero near room temperature?
Its output is tiny below about 50 °C, so cold junction errors hardly matter.
How do I use the table with a calibrator?
Set the calibrator to the mV for the test temperature with CJC off, or use the calibrator type setting with CJC on.
You May Also Like
Learn more on the blog
Thermocouple calibration: 7 proven steps
A practical guide on instrumentationblog.in that explains the theory behind this cheat sheet.
Read Full ArticleMore Cheat Sheets
4 to 20 mA Cheat SheetPrintable A4 PDFFlow Measurement Formulas Cheat SheetPrintable A4 PDFPressure Cheat SheetPrintable A4 PDFTemperature Measurement Cheat SheetPrintable A4 PDFLevel Measurement Formulas Cheat SheetPrintable A4 PDFControl Valve Cheat SheetPrintable A4 PDFElectrical Formulas Cheat SheetPrintable A4 PDFOp Amp Formulas Cheat SheetPrintable A4 PDFElectronic Component Codes Cheat SheetPrintable A4 PDFPID Tuning Cheat SheetPrintable A4 PDFISA Instrument Letter Codes Cheat SheetPrintable A4 PDFIP, NEMA and Ex Rating Cheat SheetPrintable A4 PDFSIL and Functional Safety Cheat SheetPrintable A4 PDFCalibration and Uncertainty Cheat SheetPrintable A4 PDFAnalytical Instruments Cheat SheetPrintable A4 PDFModbus and HART Cheat SheetPrintable A4 PDFPLC I/O and Signals Cheat SheetPrintable A4 PDFEngineering Units Conversion Cheat SheetPrintable A4 PDFInstrument Loop Troubleshooting Cheat SheetPrintable A4 PDF