SIL and Functional Safety Quiz
Test yourself with 20 multiple choice questions. Check your answers to get a score and an explanation for every question.
SIL and Functional Safety Quiz: 20 Questions
Choose one answer for each question, then press Check answers. Explanations appear after checking.
1. SIL 2 PFDavg range is:
2. RRF equals:
3. For 1oo1, PFDavg ≈:
4. λDU = 2 × 10⁻⁶ /h, TI = 8760 h gives PFDavg about:
5. Which failures dominate PFDavg?
6. Safe failure fraction is:
7. Under IEC 61511 Ed. 2, minimum HFT for SIL 3 is:
8. Which voting gives HFT 1 with low spurious trips?
9. The beta factor models:
10. Proof test coverage below 100 % means:
11. In LOPA, a BPCS loop can be credited with a PFD no better than:
12. Initiating 0.2 /yr with two IPLs of 0.1 gives a frequency of:
13. High demand mode uses which measure?
14. Process safety time is:
15. De energise to trip design means:
16. The document defining each SIF requirement is the:
17. A long term SIS bypass should be handled through:
18. MTBF of 500,000 h corresponds to λ of:
19. Diagnostic coverage is:
20. HAZOP uses:
About this Quiz
20 multiple choice questions on sil and functional safety, the kind asked in instrumentation interviews, technician exams and plant training. Each answer comes with a short explanation, so the quiz works as a revision sheet too.
Show answer key
- 10⁻³ to 10⁻²: RRF 100 to 1000. Learn more: Safety Integrity Level
- 1 ÷ PFDavg: Risk reduction factor is the inverse of PFDavg. Learn more: Risk Reduction Factor
- λDU × TI ÷ 2: Hidden failures build up linearly between tests. Learn more: PFDavg
- 8.8 × 10⁻³: 2e−6 × 8760 ÷ 2 = 8.76e−3, SIL 2 range. Learn more: PFDavg
- Dangerous undetected: Only proof tests find them. Learn more: Failure Rate
- (λS + λDD) ÷ λtotal: Share of failures that are safe or detected. Learn more: Safe Failure Fraction
- 1: SIL 1 and 2 (low demand) need HFT 0; SIL 3 needs 1. Learn more: Hardware Fault Tolerance
- 2oo3: 2oo3 tolerates one dangerous and one safe failure. Learn more: Voting Architecture
- Common cause failures: A fraction β of failures hit all channels together. Learn more: Common Cause Failure
- Some failures stay hidden until replacement: Uncovered failures accumulate over mission time. Learn more: Proof Test Coverage
- 0.1: IEC 61511 limits BPCS risk reduction claims. Learn more: Independent Protection Layer
- 2 × 10⁻³ /yr: 0.2 × 0.1 × 0.1. Learn more: Layers of Protection Analysis
- PFH: PFH is dangerous failures per hour. Learn more: PFH
- Time from fault to hazardous event without action: The SIF must act well within it. Learn more: Process Safety Time
- Loss of power causes the trip: Wiring and power failures fail safe. Learn more: Safe State
- Safety requirements specification: SRS per IEC 61511. Learn more: Safety Requirements Specification
- Management of change: Bypass procedures and MOC control risk. Learn more: Safety Bypass
- 2 × 10⁻⁶ /h: λ = 1 ÷ MTBF. Learn more: Mean Time Between Failures
- λDD ÷ (λDD + λDU): Fraction of dangerous failures detected online. Learn more: Diagnostic Coverage
- Guide words applied to process parameters: No, more, less, reverse and so on. Learn more: HAZOP
Frequently Asked Questions
Is this quiz free?
Yes. No sign up is needed and you can retake it as often as you like.
Are the answers explained?
Yes. After you check your answers, each question shows the correct answer and a short explanation.
Where can I find more questions?
See the Interview Q&A section of instrumentationblog.in and the linked article below.
Learn more on the blog
What is SIL (safety integrity level)
A practical, field focused guide on instrumentationblog.in that explains the theory behind this tool and how engineers apply it on real plants.
Read Full Article