Control Valve Sizing Quiz
Test yourself with 20 multiple choice questions. Check your answers to get a score and an explanation for every question.
Control Valve Sizing Quiz: 20 Questions
Choose one answer for each question, then press Check answers. Explanations appear after checking.
1. Cv is the flow of water in US gpm at a pressure drop of:
2. Cv and Kv are related by:
3. Water 50 m³/h at 1 bar drop needs a Kv of:
4. Which characteristic is most common for process control valves?
5. Valve authority is:
6. With low authority a linear valve behaves like:
7. Cavitation damage looks like:
8. Flashing occurs when outlet pressure is:
9. Which valve type has the highest FL (lowest pressure recovery)?
10. Liquid choked ΔP equals:
11. Class IV seat leakage allows:
12. Air to open valves fail:
13. A positioner mainly:
14. An I/P converter at 12 mA outputs about:
15. Valve stiction causes:
16. Two Cv 40 valves in parallel give:
17. Partial stroke testing typically moves an ESD valve:
18. Bench set means:
19. A volume booster is used to:
20. Graphite packing compared with PTFE has:
About this Quiz
20 multiple choice questions on control valve sizing, the kind asked in instrumentation interviews, technician exams and plant training. Each answer comes with a short explanation, so the quiz works as a revision sheet too.
Show answer key
- 1 psi: Kv uses m³/h at 1 bar. Learn more: Flow Coefficient (Cv)
- Cv = 1.156 Kv: Conversion of units. Learn more: Kv Flow Factor
- 50: Kv = Q √(SG ÷ ΔP) = 50; Cv would be 57.8. Learn more: Kv Flow Factor
- Equal percentage: It compensates falling valve ΔP as flow rises. Learn more: Valve Characteristic
- Valve ΔP ÷ total system ΔP: Higher authority keeps the characteristic undistorted. Learn more: Valve Authority
- Quick opening: Most flow change happens early in travel. Learn more: Installed Characteristic
- Rough, cinder like pitting: Collapsing bubbles hammer the surface. Learn more: Cavitation
- Below the vapour pressure: The vapour does not collapse. Learn more: Flashing
- Globe: Globe FL about 0.9; rotary about 0.55 to 0.7. Learn more: Liquid Pressure Recovery Factor
- FL² × (P1 − FF Pv): IEC 60534-2-1 liquid choking. Learn more: Choked Flow
- 0.01 % of rated capacity: Class II 0.5 %, III 0.1 %, IV 0.01 %. Learn more: Seat Leakage Class
- Closed: Spring closes the valve on air loss. Learn more: Air to Open
- Matches stem position to the control signal: It overcomes friction and process forces. Learn more: Valve Positioner
- 0.6 bar (9 psi): 0.2 + 0.8 × 0.5 = 0.6 bar. Learn more: I/P Converter
- Stick slip and loop cycling: The valve jumps past the target then sticks again. Learn more: Valve Stiction
- Cv 80: Parallel Cv values add. Learn more: Flow Coefficient (Cv)
- About 10 to 20 % of travel: Enough to prove movement without upsetting the process. Learn more: Partial Stroke Testing
- Spring range measured with no process load: Air pressure range for full stroke on the bench. Learn more: Spring Range
- Stroke large actuators faster: It supplies large air flow following the positioner signal. Learn more: Volume Booster
- Higher temperature limit and more friction: Graphite handles heat but adds friction. Learn more: Valve Packing
Frequently Asked Questions
Is this quiz free?
Yes. No sign up is needed and you can retake it as often as you like.
Are the answers explained?
Yes. After you check your answers, each question shows the correct answer and a short explanation.
Where can I find more questions?
See the Interview Q&A section of instrumentationblog.in and the linked article below.
Learn more on the blog
Control valve flow coefficient (Cv and Kv)
A practical, field focused guide on instrumentationblog.in that explains the theory behind this tool and how engineers apply it on real plants.
Read Full Article