DP Level and Guided Wave Radar Fault Finding Guide

A one page guide to DP and guided wave radar level problems: density changes, wet legs and seals, ranges, interface and probe coating.

One page A4Vendor neutralFree, no sign up

Download

DP Level and Guided Wave Radar Fault Finding Guide PDF preview

A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.

Download PDF A4 · 56 KB

Before you start

  • Permit, isolation and control room informed.
  • Put the loop in manual or inhibit trips as authorised.
  • Use certified test equipment in hazardous areas.
  • Record as found readings before changing anything.

Quick checks

  • Wet legs full, seals intact?
  • Density used in range matches product?
  • GWR echo curve saved?
  • Compare with gauge glass or dip.
Advertisement

Symptoms, causes and fixes

SymptomLikely causesChecks and fixes
DP level reads highWet leg partly empty, higher density, blocked LPRefill leg; check density; clear LP tap
DP level reads lowLower density, gas in HP line, blocked HPCheck density; vent HP; clear tap
Drift with ambientRemote seal capillaries in sun, unequal lengthsShade and insulate capillaries
Wrong after product changeRange calculated for old densityRecalculate LRV and URV
GWR reads end of probeLow dielectric, coating, wrong probe lengthCheck dielectric and probe settings
GWR interface wrongEmulsion layer, wrong upper dielectricCheck settings; sample to confirm layers
Advertisement

Formulas

  • h = ΔP ÷ (ρ g).
  • Wet leg offset = ρleg g Hleg.
  • 1 m water ≈ 98.07 mbar.

NAMUR NE107 status

StatusMeaningAction
F FailureOutput invalidRepair or replace; check loop goes to safe state
C Function checkSimulation, calibration or maintenance activeFinish the work, return to normal mode
S Out of specificationOperating outside limits or uncertainCheck process conditions and sensor
M Maintenance requiredStill valid but degradingPlan maintenance before failure

Related Tools, Procedures and Calculators

Frequently Asked Questions

Why is my level wrong after a product change?

DP level depends on density; recalculate the range.

Why do seals drift in sun?

Fill fluid expands unequally in the capillaries.

What dielectric does GWR need?

It depends on probe type; coaxial probes handle the lowest values.