DP Flow Measurement Fault Finding Guide
A one page guide to DP flow problems: impulse line faults, square root and cutoff settings, orifice condition and installation effects.
One page A4Vendor neutralFree, no sign up
Download
A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.
Download PDF A4 · 54 KBBefore you start
- Permit, isolation and control room informed.
- Put the loop in manual or inhibit trips as authorised.
- Use certified test equipment in hazardous areas.
- Record as found readings before changing anything.
Quick checks
- Equaliser closed, HP and LP open?
- Legs full (liquid) or drained (gas)?
- Square root in one place only?
- Plate direction and bore correct?
Advertisement
Symptoms, causes and fixes
| Symptom | Likely causes | Checks and fixes |
|---|---|---|
| Reads low | Gas in liquid legs, HP side leak or plug, worn orifice edge, orifice installed reversed | Vent legs; check HP valves and tap; inspect plate edge and direction |
| Reads high | LP side leak or plug, liquid in gas legs, wrong bore or range | Check LP side; drain gas legs; verify bore and range |
| Flow shown at zero | No low flow cutoff, equaliser passing, zero shift | Set cutoff; check equaliser; zero at line pressure |
| Flow far too high at low DP | Square root applied twice (transmitter and DCS) | Apply square root in one place only |
| Noisy | Pulsation, two phase flow, short straight run | Damping; check process; verify straight run |
| Slowly drifting | Plugging taps, condensate level changing in steam legs | Blow down; keep condensate pots full and equal |
| Wrong after rerange | DCS scaling or totaliser not updated | Update all settings and data sheet |
Advertisement
Rules of thumb
- Flow % = √(DP %) × 10.
- 25 % DP = 50 % flow = 12 mA (square root output).
- Liquid service: transmitter below taps; gas service: above taps.
- Steam: condensate pots at equal height.
Related Tools, Procedures and Calculators
Frequently Asked Questions
Why does my orifice read low?
Gas trapped in liquid impulse lines or an HP side problem are the usual causes.
How do I check square root settings?
At 25 % DP the flow should be 50 %; if it shows about 71 %, square root is applied twice.
Does a worn orifice read high or low?
A rounded edge raises the discharge coefficient, so the meter reads low.
You May Also Like
Learn more on the blog
Mistakes in DP flow measurement
A practical guide on instrumentationblog.in with more background on this equipment.
Read Full ArticleMore Fault Finding Guides
Pressure Transmitter Fault Finding GuidePrintable A4 PDFMagnetic Flowmeter Fault Finding GuidePrintable A4 PDFCoriolis Flowmeter Fault Finding GuidePrintable A4 PDFVortex and Ultrasonic Flowmeter Fault Finding GuidePrintable A4 PDFRadar and Ultrasonic Level Fault Finding GuidePrintable A4 PDFDP Level and Guided Wave Radar Fault Finding GuidePrintable A4 PDFTemperature Measurement Fault Finding GuidePrintable A4 PDFControl Valve and Positioner Fault Finding GuidePrintable A4 PDFOn Off and ESD Valve Fault Finding GuidePrintable A4 PDFpH and Conductivity Analyser Fault Finding GuidePrintable A4 PDFFixed Gas Detector Fault Finding GuidePrintable A4 PDFPLC Analog Input Fault Finding GuidePrintable A4 PDFModbus and HART Communication Fault Finding GuidePrintable A4 PDFVFD Fault Finding Guide (Vendor Neutral)Printable A4 PDFNAMUR NE107 Diagnostic Status GuidePrintable A4 PDF