Fault Finding Guides · Free PDF

DP Flow Measurement Fault Finding Guide

A one page guide to DP flow problems: impulse line faults, square root and cutoff settings, orifice condition and installation effects.

One page A4Vendor neutralFree, no sign up

Download

DP Flow Measurement Fault Finding Guide PDF preview

A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.

Download PDF A4 · 54 KB

Before you start

  • Permit, isolation and control room informed.
  • Put the loop in manual or inhibit trips as authorised.
  • Use certified test equipment in hazardous areas.
  • Record as found readings before changing anything.

Quick checks

  • Equaliser closed, HP and LP open?
  • Legs full (liquid) or drained (gas)?
  • Square root in one place only?
  • Plate direction and bore correct?
Advertisement

Symptoms, causes and fixes

SymptomLikely causesChecks and fixes
Reads lowGas in liquid legs, HP side leak or plug, worn orifice edge, orifice installed reversedVent legs; check HP valves and tap; inspect plate edge and direction
Reads highLP side leak or plug, liquid in gas legs, wrong bore or rangeCheck LP side; drain gas legs; verify bore and range
Flow shown at zeroNo low flow cutoff, equaliser passing, zero shiftSet cutoff; check equaliser; zero at line pressure
Flow far too high at low DPSquare root applied twice (transmitter and DCS)Apply square root in one place only
NoisyPulsation, two phase flow, short straight runDamping; check process; verify straight run
Slowly driftingPlugging taps, condensate level changing in steam legsBlow down; keep condensate pots full and equal
Wrong after rerangeDCS scaling or totaliser not updatedUpdate all settings and data sheet
Advertisement

Rules of thumb

  • Flow % = √(DP %) × 10.
  • 25 % DP = 50 % flow = 12 mA (square root output).
  • Liquid service: transmitter below taps; gas service: above taps.
  • Steam: condensate pots at equal height.

Related Tools, Procedures and Calculators

Frequently Asked Questions

Why does my orifice read low?

Gas trapped in liquid impulse lines or an HP side problem are the usual causes.

How do I check square root settings?

At 25 % DP the flow should be 50 %; if it shows about 71 %, square root is applied twice.

Does a worn orifice read high or low?

A rounded edge raises the discharge coefficient, so the meter reads low.