Radar and Ultrasonic Level Fault Finding Guide
A one page guide to non contact level problems: lost echoes, false echoes, foam, condensation, buildup and configuration.
One page A4Vendor neutralFree, no sign up
Download
A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.
Download PDF A4 · 53 KBBefore you start
- Permit, isolation and control room informed.
- Put the loop in manual or inhibit trips as authorised.
- Use certified test equipment in hazardous areas.
- Record as found readings before changing anything.
Quick checks
- Save the echo curve first.
- Reference height and units correct?
- Antenna clean and dry?
- Mapping done at low level?
Advertisement
Symptoms, causes and fixes
| Symptom | Likely causes | Checks and fixes |
|---|---|---|
| Lost echo | Foam, turbulence, low dielectric, antenna buildup | Check echo curve; clean antenna; consider GWR or stilling well |
| Reads constant level | Locked on a false echo from internals | Redo false echo mapping at low level |
| Reads full when empty | Echo inside blocking distance, condensation on antenna | Check blocking distance; heat or purge antenna |
| Jumps between values | Agitator, filling stream, multiple echoes | Move sensor; map; increase damping slightly |
| Ultrasonic reads wrong in closed tank | Vapour changes speed of sound, temperature gradient | Use radar; check temperature compensation |
| Offset error | Wrong reference height or tank height | Measure ullage manually; correct reference |
Advertisement
NAMUR NE107 status
| Status | Meaning | Action |
|---|---|---|
| F Failure | Output invalid | Repair or replace; check loop goes to safe state |
| C Function check | Simulation, calibration or maintenance active | Finish the work, return to normal mode |
| S Out of specification | Operating outside limits or uncertain | Check process conditions and sensor |
| M Maintenance required | Still valid but degrading | Plan maintenance before failure |
Related Tools, Procedures and Calculators
Frequently Asked Questions
What is false echo mapping?
Recording fixed echoes from internals so the transmitter ignores them.
Why does foam cause problems?
Foam can absorb or scatter the signal.
When should GWR replace radar?
For foam, low dielectric, chambers and interface measurement.
You May Also Like
Learn more on the blog
Guided wave radar vs non contact radar
A practical guide on instrumentationblog.in with more background on this equipment.
Read Full ArticleMore Fault Finding Guides
Pressure Transmitter Fault Finding GuidePrintable A4 PDFDP Flow Measurement Fault Finding GuidePrintable A4 PDFMagnetic Flowmeter Fault Finding GuidePrintable A4 PDFCoriolis Flowmeter Fault Finding GuidePrintable A4 PDFVortex and Ultrasonic Flowmeter Fault Finding GuidePrintable A4 PDFDP Level and Guided Wave Radar Fault Finding GuidePrintable A4 PDFTemperature Measurement Fault Finding GuidePrintable A4 PDFControl Valve and Positioner Fault Finding GuidePrintable A4 PDFOn Off and ESD Valve Fault Finding GuidePrintable A4 PDFpH and Conductivity Analyser Fault Finding GuidePrintable A4 PDFFixed Gas Detector Fault Finding GuidePrintable A4 PDFPLC Analog Input Fault Finding GuidePrintable A4 PDFModbus and HART Communication Fault Finding GuidePrintable A4 PDFVFD Fault Finding Guide (Vendor Neutral)Printable A4 PDFNAMUR NE107 Diagnostic Status GuidePrintable A4 PDF