Before you start

  • Permit, isolation and control room informed.
  • Put the loop in manual or inhibit trips as authorised.
  • Use certified test equipment in hazardous areas.
  • Record as found readings before changing anything.

Quick checks

  • Air supply and solenoid power present?
  • Stroke time within the safety requirement?
  • Limit switches set at full open and closed?
  • Last proof test result?
Advertisement

Symptoms, causes and fixes

SymptomLikely causesChecks and fixes
Does not close on tripSolenoid stuck, exhaust blocked, seized valve, high frictionTest solenoid; clear vents; stroke test
Slow closingSmall solenoid Cv, blocked exhaust, long tubingCheck air path; fit quick exhaust
No closed feedbackLimit switch misaligned or failed, cable faultAdjust cam; test switch; check wiring
Partial stroke test failsSticking, high breakaway torque, wrong test settingsFull stroke test; inspect actuator and valve
Leaks when closedSeat damage, debrisLeak test; repair seats
Solenoid coil faultOverheating, wrong voltage, water ingressCheck voltage and coil resistance; replace
Advertisement

Remember

  • Record as found stroke times before maintenance.
  • Stroke time must fit within the process safety time.
  • A failed proof test needs reporting and review.

Related Tools, Procedures and Calculators

Frequently Asked Questions

Why record stroke time?

A rising stroke time warns of sticking before the valve fails to close.

Does a partial stroke test replace a full test?

No, it detects many failures but not seat leakage or full travel problems.

What closes an ESD valve on trip?

Usually the solenoid vents the actuator and the spring closes the valve.