Pressure Transmitter Fault Finding Guide

A one page guide to find pressure transmitter faults fast: quick checks, symptoms with likely causes and fixes, and NAMUR NE107 status meanings.

One page A4Vendor neutralFree, no sign up

Download

Pressure Transmitter Fault Finding Guide PDF preview

A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.

Download PDF A4 · 53 KB

Before you start

  • Permit, isolation and control room informed.
  • Put the loop in manual or inhibit trips as authorised.
  • Use certified test equipment in hazardous areas.
  • Record as found readings before changing anything.

Quick checks

  • Loop current matches DCS reading?
  • Transmitter display matches process (test gauge)?
  • Root valves open, manifold correct?
  • Recent work, weather or process change?
Advertisement

Symptoms, causes and fixes

SymptomLikely causesChecks and fixes
No output (0 mA)No loop power, open wire, blown fuse, reversed polarityMeasure supply and terminal voltage; check fuses and polarity
Reads high or low constantlyZero shift, wrong range, head from mounting, blocked tapCompare with test gauge; check LRV and URV; zero trim at known pressure
Reading frozenRoot valve closed, plugged impulse line, fixed current modeOpen and blow down tap; check loop test mode off
Noisy readingPulsation, gas in liquid line, grounding, low dampingAdd damping or snubber; vent lines; check shield grounding
Slow responseLong or partly blocked impulse line, high damping, frozen lineCheck damping; clear line; check heat tracing
Drifts with weatherBlocked vent on gauge sensor, sealed sensor, sun on sealClean vent; shade seals; check sensor type
Reads after overpressureSensor damage beyond overpressure limitCheck zero; replace if outside spec
Advertisement

NAMUR NE107 status

StatusMeaningAction
F FailureOutput invalidRepair or replace; check loop goes to safe state
C Function checkSimulation, calibration or maintenance activeFinish the work, return to normal mode
S Out of specificationOperating outside limits or uncertainCheck process conditions and sensor
M Maintenance requiredStill valid but degradingPlan maintenance before failure

Related Tools, Procedures and Calculators

Frequently Asked Questions

Why does my transmitter read high after mounting?

Liquid in the impulse line adds head; transmitters below the tap read high.

How do I zero a gauge pressure transmitter?

Isolate, vent to atmosphere and use zero trim; never zero against process pressure.

Can a blocked vent cause errors?

Yes, on gauge sensors the reference side must see atmosphere.