Download PDF A4 · 53 KBBefore you start
- Permit, isolation and control room informed.
- Put the loop in manual or inhibit trips as authorised.
- Use certified test equipment in hazardous areas.
- Record as found readings before changing anything.
Quick checks
- Read the detailed diagnostic behind the status.
- Map statuses to alarms and maintenance work orders.
- Do not suppress F status at the DCS.
Advertisement
Symptoms, causes and fixes
| Symptom | Likely causes | Checks and fixes |
|---|---|---|
| F: Failure | Device or process fault, output not valid | Treat measurement as bad; repair |
| C: Function check | Local work: simulation, calibration, configuration | Confirm work in progress; return to normal |
| S: Out of specification | Outside measuring limits or uncertain conditions | Check process conditions and installation |
| M: Maintenance required | Valid but wear or drift detected | Plan maintenance before failure |
Advertisement
Related NAMUR NE43 current levels
| Current | Meaning |
|---|---|
| 3.8 to 20.5 mA | Valid measurement |
| ≤ 3.6 mA | Failure downscale |
| ≥ 21.0 mA | Failure upscale |
Related Tools, Procedures and Calculators
Frequently Asked Questions
What is NAMUR NE107?
A recommendation that groups device diagnostics into four status signals with standard symbols and colours.
How does NE107 relate to NE43?
NE43 defines fault currents on 4 to 20 mA; NE107 defines status categories, mostly sent digitally.
Should C status alarm operators?
It should inform them that the device is under maintenance.
You May Also Like
Learn more on the blog
HART protocol: how it works and how to use a HART communicator
A practical guide on instrumentationblog.in with more background on this equipment.
Read Full ArticleMore Fault Finding Guides
Pressure Transmitter Fault Finding GuidePrintable A4 PDFDP Flow Measurement Fault Finding GuidePrintable A4 PDFMagnetic Flowmeter Fault Finding GuidePrintable A4 PDFCoriolis Flowmeter Fault Finding GuidePrintable A4 PDFVortex and Ultrasonic Flowmeter Fault Finding GuidePrintable A4 PDFRadar and Ultrasonic Level Fault Finding GuidePrintable A4 PDFDP Level and Guided Wave Radar Fault Finding GuidePrintable A4 PDFTemperature Measurement Fault Finding GuidePrintable A4 PDFControl Valve and Positioner Fault Finding GuidePrintable A4 PDFOn Off and ESD Valve Fault Finding GuidePrintable A4 PDFpH and Conductivity Analyser Fault Finding GuidePrintable A4 PDFFixed Gas Detector Fault Finding GuidePrintable A4 PDFPLC Analog Input Fault Finding GuidePrintable A4 PDFModbus and HART Communication Fault Finding GuidePrintable A4 PDFVFD Fault Finding Guide (Vendor Neutral)Printable A4 PDF
Advertisement