PLC Analog Input Fault Finding Guide

A one page guide to PLC and DCS analog input problems: scaling, wiring type, noise, ground loops and channel faults.

One page A4Vendor neutralFree, no sign up

Download

PLC Analog Input Fault Finding Guide PDF preview

A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.

Download PDF A4 · 53 KB

Before you start

  • Permit, isolation and control room informed.
  • Put the loop in manual or inhibit trips as authorised.
  • Use certified test equipment in hazardous areas.
  • Record as found readings before changing anything.

Quick checks

  • Measure loop current at the card.
  • Compare raw counts with expected.
  • Check card diagnostics and forces.
  • Check shield grounding.
Advertisement

Symptoms, causes and fixes

SymptomLikely causesChecks and fixes
Value wrong but mA correctScaling, raw range or units wrongCheck raw limits (e.g. 0 to 27648) and LRV, URV
Overrange or underrange alarmSignal outside card limits, open wireMeasure mA; check wiring
Two channels interfereMixed 2 and 4 wire devices on shared common, ground loopWire per card manual; isolate
Noisy valueShield earthed both ends, VFD cables nearby, no filterSingle point shield; segregate; filter
Stuck valueChannel or module fault, forced valueCheck module status and forces
HART not passingCard not HART capable, low loop resistanceCheck card type; add resistance
Advertisement

Formulas

  • Value = LRV + (raw − rawmin) ÷ (rawmax − rawmin) × span.
  • mA = 4 + 16 × %.
  • Size loops for 22 mA.

Related Tools, Procedures and Calculators

Frequently Asked Questions

Why is my PLC value wrong when mA is right?

The scaling or raw count range in the program does not match the card.

Can I mix 2 and 4 wire transmitters?

Only if the card allows it; wrong wiring on a shared common causes errors.

Where should the shield be earthed?

Usually at the control system end only.