Temperature Measurement Fault Finding Guide

A one page guide to temperature measurement problems with thermocouples, RTDs and transmitters.

One page A4Vendor neutralFree, no sign up

Download

Temperature Measurement Fault Finding Guide PDF preview

A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.

Download PDF A4 · 54 KB

Before you start

  • Permit, isolation and control room informed.
  • Put the loop in manual or inhibit trips as authorised.
  • Use certified test equipment in hazardous areas.
  • Record as found readings before changing anything.

Quick checks

  • Sensor type and wiring match configuration?
  • Resistance or mV at ambient sensible?
  • Element touches well bottom?
  • Compare with a portable probe.
Advertisement

Symptoms, causes and fixes

SymptomLikely causesChecks and fixes
Reads upscale or faultOpen element or wire, burnout detectionCheck continuity at head; replace element
Moves wrong wayThermocouple polarity reversedSwap at transmitter; check colour code
Few °C offset (TC)Copper or wrong extension cable, CJC errorUse correct cable to CJC point
Few °C offset (RTD)2 wire leads, wrong alpha or sensor type, mismatched 3 wire leadsCheck wiring and configuration
Reads near ambientElement not reaching well bottom, wrong lengthSpring load element; check length
Slow responseAir gap in thermowell, heavy wellFit correct element; consider tapered well
NoisyGrounded TC with earth loop, VFD noiseUse isolated transmitter; shield and segregate
Advertisement

Quick values

  • Pt100: 100 Ω at 0 °C, 109.73 Ω at 25 °C, 138.51 Ω at 100 °C.
  • Type K: about 1.0 mV at 25 °C, 4.096 mV at 100 °C.
  • Add CJC in mV, never in °C.

Related Tools, Procedures and Calculators

Frequently Asked Questions

Why does a thermocouple read room temperature?

Often an open circuit without burnout detection, or the element is not in the well.

How do I check a Pt100 quickly?

Measure resistance and compare with the table.

Why is my TC reading wrong by a few degrees?

Wrong extension cable or a cold junction error are common causes.