Temperature Measurement Fault Finding Guide
A one page guide to temperature measurement problems with thermocouples, RTDs and transmitters.
One page A4Vendor neutralFree, no sign up
Download
A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.
Download PDF A4 · 54 KBBefore you start
- Permit, isolation and control room informed.
- Put the loop in manual or inhibit trips as authorised.
- Use certified test equipment in hazardous areas.
- Record as found readings before changing anything.
Quick checks
- Sensor type and wiring match configuration?
- Resistance or mV at ambient sensible?
- Element touches well bottom?
- Compare with a portable probe.
Advertisement
Symptoms, causes and fixes
| Symptom | Likely causes | Checks and fixes |
|---|---|---|
| Reads upscale or fault | Open element or wire, burnout detection | Check continuity at head; replace element |
| Moves wrong way | Thermocouple polarity reversed | Swap at transmitter; check colour code |
| Few °C offset (TC) | Copper or wrong extension cable, CJC error | Use correct cable to CJC point |
| Few °C offset (RTD) | 2 wire leads, wrong alpha or sensor type, mismatched 3 wire leads | Check wiring and configuration |
| Reads near ambient | Element not reaching well bottom, wrong length | Spring load element; check length |
| Slow response | Air gap in thermowell, heavy well | Fit correct element; consider tapered well |
| Noisy | Grounded TC with earth loop, VFD noise | Use isolated transmitter; shield and segregate |
Advertisement
Quick values
- Pt100: 100 Ω at 0 °C, 109.73 Ω at 25 °C, 138.51 Ω at 100 °C.
- Type K: about 1.0 mV at 25 °C, 4.096 mV at 100 °C.
- Add CJC in mV, never in °C.
Related Tools, Procedures and Calculators
Frequently Asked Questions
Why does a thermocouple read room temperature?
Often an open circuit without burnout detection, or the element is not in the well.
How do I check a Pt100 quickly?
Measure resistance and compare with the table.
Why is my TC reading wrong by a few degrees?
Wrong extension cable or a cold junction error are common causes.
You May Also Like
Learn more on the blog
Thermocouple and RTD installation precautions
A practical guide on instrumentationblog.in with more background on this equipment.
Read Full ArticleMore Fault Finding Guides
Pressure Transmitter Fault Finding GuidePrintable A4 PDFDP Flow Measurement Fault Finding GuidePrintable A4 PDFMagnetic Flowmeter Fault Finding GuidePrintable A4 PDFCoriolis Flowmeter Fault Finding GuidePrintable A4 PDFVortex and Ultrasonic Flowmeter Fault Finding GuidePrintable A4 PDFRadar and Ultrasonic Level Fault Finding GuidePrintable A4 PDFDP Level and Guided Wave Radar Fault Finding GuidePrintable A4 PDFControl Valve and Positioner Fault Finding GuidePrintable A4 PDFOn Off and ESD Valve Fault Finding GuidePrintable A4 PDFpH and Conductivity Analyser Fault Finding GuidePrintable A4 PDFFixed Gas Detector Fault Finding GuidePrintable A4 PDFPLC Analog Input Fault Finding GuidePrintable A4 PDFModbus and HART Communication Fault Finding GuidePrintable A4 PDFVFD Fault Finding Guide (Vendor Neutral)Printable A4 PDFNAMUR NE107 Diagnostic Status GuidePrintable A4 PDF