Vortex and Ultrasonic Flowmeter Fault Finding Guide
A one page guide to vortex and ultrasonic meter problems: low Reynolds number, vibration, signal quality, pipe data and installation.
One page A4Vendor neutralFree, no sign up
Download
A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.
Download PDF A4 · 54 KBBefore you start
- Permit, isolation and control room informed.
- Put the loop in manual or inhibit trips as authorised.
- Use certified test equipment in hazardous areas.
- Record as found readings before changing anything.
Quick checks
- Configuration matches certificate (K factor, ID)?
- Flow above minimum for the meter?
- Ultrasonic: signal strength and quality OK?
- Straight run as required?
Advertisement
Symptoms, causes and fixes
| Symptom | Likely causes | Checks and fixes |
|---|---|---|
| Vortex reads zero at low flow | Below minimum velocity or Reynolds number, cutoff high | Check sizing; consider smaller meter; review cutoff |
| Vortex reads with no flow | Pipe vibration counted as vortices | Adjust filter or trigger level; improve supports |
| Vortex reads low | Wrong K factor or ID, two phase flow, short straight run | Check configuration; check process; straight run |
| Ultrasonic no signal | Air, solids, poor coupling, wrong spacing | Recouple sensors; check spacing and pipe data |
| Ultrasonic reads wrong | Wrong pipe OD, wall, material or liner | Measure wall thickness; correct pipe data |
| Ultrasonic unstable | Short straight run, partly full pipe | Move sensors; check fill; use two paths |
Advertisement
NAMUR NE107 status
| Status | Meaning | Action |
|---|---|---|
| F Failure | Output invalid | Repair or replace; check loop goes to safe state |
| C Function check | Simulation, calibration or maintenance active | Finish the work, return to normal mode |
| S Out of specification | Operating outside limits or uncertain | Check process conditions and sensor |
| M Maintenance required | Still valid but degrading | Plan maintenance before failure |
Related Tools, Procedures and Calculators
Frequently Asked Questions
Why does a vortex meter stop at low flow?
Vortices become weak below a minimum Reynolds number, so the meter cuts off.
Why does a clamp on meter need wall thickness?
It calculates the sound path and flow area from pipe dimensions.
Can vibration cause false flow?
Yes, on vortex meters.
You May Also Like
Learn more on the blog
Types of flow meters
A practical guide on instrumentationblog.in with more background on this equipment.
Read Full ArticleMore Fault Finding Guides
Pressure Transmitter Fault Finding GuidePrintable A4 PDFDP Flow Measurement Fault Finding GuidePrintable A4 PDFMagnetic Flowmeter Fault Finding GuidePrintable A4 PDFCoriolis Flowmeter Fault Finding GuidePrintable A4 PDFRadar and Ultrasonic Level Fault Finding GuidePrintable A4 PDFDP Level and Guided Wave Radar Fault Finding GuidePrintable A4 PDFTemperature Measurement Fault Finding GuidePrintable A4 PDFControl Valve and Positioner Fault Finding GuidePrintable A4 PDFOn Off and ESD Valve Fault Finding GuidePrintable A4 PDFpH and Conductivity Analyser Fault Finding GuidePrintable A4 PDFFixed Gas Detector Fault Finding GuidePrintable A4 PDFPLC Analog Input Fault Finding GuidePrintable A4 PDFModbus and HART Communication Fault Finding GuidePrintable A4 PDFVFD Fault Finding Guide (Vendor Neutral)Printable A4 PDFNAMUR NE107 Diagnostic Status GuidePrintable A4 PDF