Vortex and Ultrasonic Flowmeter Fault Finding Guide

A one page guide to vortex and ultrasonic meter problems: low Reynolds number, vibration, signal quality, pipe data and installation.

One page A4Vendor neutralFree, no sign up

Download

Vortex and Ultrasonic Flowmeter Fault Finding Guide PDF preview

A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.

Download PDF A4 · 54 KB

Before you start

  • Permit, isolation and control room informed.
  • Put the loop in manual or inhibit trips as authorised.
  • Use certified test equipment in hazardous areas.
  • Record as found readings before changing anything.

Quick checks

  • Configuration matches certificate (K factor, ID)?
  • Flow above minimum for the meter?
  • Ultrasonic: signal strength and quality OK?
  • Straight run as required?
Advertisement

Symptoms, causes and fixes

SymptomLikely causesChecks and fixes
Vortex reads zero at low flowBelow minimum velocity or Reynolds number, cutoff highCheck sizing; consider smaller meter; review cutoff
Vortex reads with no flowPipe vibration counted as vorticesAdjust filter or trigger level; improve supports
Vortex reads lowWrong K factor or ID, two phase flow, short straight runCheck configuration; check process; straight run
Ultrasonic no signalAir, solids, poor coupling, wrong spacingRecouple sensors; check spacing and pipe data
Ultrasonic reads wrongWrong pipe OD, wall, material or linerMeasure wall thickness; correct pipe data
Ultrasonic unstableShort straight run, partly full pipeMove sensors; check fill; use two paths
Advertisement

NAMUR NE107 status

StatusMeaningAction
F FailureOutput invalidRepair or replace; check loop goes to safe state
C Function checkSimulation, calibration or maintenance activeFinish the work, return to normal mode
S Out of specificationOperating outside limits or uncertainCheck process conditions and sensor
M Maintenance requiredStill valid but degradingPlan maintenance before failure

Related Tools, Procedures and Calculators

Frequently Asked Questions

Why does a vortex meter stop at low flow?

Vortices become weak below a minimum Reynolds number, so the meter cuts off.

Why does a clamp on meter need wall thickness?

It calculates the sound path and flow area from pipe dimensions.

Can vibration cause false flow?

Yes, on vortex meters.