Fixed Gas Detector Fault Finding Guide
A one page guide to fixed gas detector problems: bump test failures, poisoning, drift, false alarms and output faults.
One page A4Vendor neutralFree, no sign up
Download
A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.
Download PDF A4 · 52 KBBefore you start
- Permit, isolation and control room informed.
- Put the loop in manual or inhibit trips as authorised.
- Use certified test equipment in hazardous areas.
- Record as found readings before changing anything.
Quick checks
- Test gas correct and in date?
- Inhibit status known?
- Sensor within service life?
- Environment: dust, water, steam?
Advertisement
Symptoms, causes and fixes
| Symptom | Likely causes | Checks and fixes |
|---|---|---|
| Fails bump test (low) | Poisoned catalytic sensor, blocked sinter, aged sensor | Clean or replace; calibrate |
| False alarms | Cross sensitive gases, humidity, steam, RF | Check process; relocate; filter |
| Negative or drifting zero | Calibrated in contaminated air, sensor ageing | Zero with zero gas; replace sensor |
| IR optics fault | Dirty windows, condensation | Clean optics; fit weather guard |
| No signal at DCS | Loop fault, inhibit left on | Check loop and inhibit status |
| Slow response | Blocked guard or sinter, long sampling line | Clean; check flow |
Advertisement
Reminders
- Methane LEL 4.4 % vol (IEC 60079-20-1).
- Catalytic sensors need oxygen and can be poisoned by silicones.
- IR detectors do not detect hydrogen.
Related Tools, Procedures and Calculators
Frequently Asked Questions
Why does a catalytic detector read low?
Poisoning or inhibition by silicones, sulfur compounds or lead.
What is a bump test?
A quick gas exposure to prove response without adjustment.
Why do IR detectors give optics faults?
Dirt or condensation on the optical windows.
You May Also Like
Learn more on the blog
Hazardous area classification zones
A practical guide on instrumentationblog.in with more background on this equipment.
Read Full ArticleMore Fault Finding Guides
Pressure Transmitter Fault Finding GuidePrintable A4 PDFDP Flow Measurement Fault Finding GuidePrintable A4 PDFMagnetic Flowmeter Fault Finding GuidePrintable A4 PDFCoriolis Flowmeter Fault Finding GuidePrintable A4 PDFVortex and Ultrasonic Flowmeter Fault Finding GuidePrintable A4 PDFRadar and Ultrasonic Level Fault Finding GuidePrintable A4 PDFDP Level and Guided Wave Radar Fault Finding GuidePrintable A4 PDFTemperature Measurement Fault Finding GuidePrintable A4 PDFControl Valve and Positioner Fault Finding GuidePrintable A4 PDFOn Off and ESD Valve Fault Finding GuidePrintable A4 PDFpH and Conductivity Analyser Fault Finding GuidePrintable A4 PDFPLC Analog Input Fault Finding GuidePrintable A4 PDFModbus and HART Communication Fault Finding GuidePrintable A4 PDFVFD Fault Finding Guide (Vendor Neutral)Printable A4 PDFNAMUR NE107 Diagnostic Status GuidePrintable A4 PDF