VFD Fault Finding Guide (Vendor Neutral)
A vendor neutral guide to common variable frequency drive faults by type: causes and checks that apply to most drives. Use your drive manual for exact codes.
One page A4Vendor neutralFree, no sign up
Download
A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.
Download PDF A4 · 51 KBBefore you start
- Permit, isolation and control room informed.
- Put the loop in manual or inhibit trips as authorised.
- Use certified test equipment in hazardous areas.
- Record as found readings before changing anything.
Quick checks
- Read the fault code and its history.
- Isolate and wait for DC bus discharge before touching.
- Check motor and cable insulation disconnected from the drive.
- Review ramps and motor parameters.
Advertisement
Symptoms, causes and fixes
| Symptom | Likely causes | Checks and fixes |
|---|---|---|
| Overcurrent | Too short acceleration, motor or cable short, mechanical jam | Increase ramp; megger motor and cable; check load |
| Overvoltage (DC bus) | Too short deceleration, overhauling load, high supply | Increase decel; add braking resistor; check supply |
| Undervoltage | Supply dip, loose input, failed rectifier or fuse | Check supply and input terminals |
| Overtemperature | Blocked fan or filter, high ambient, overload | Clean; improve cooling; check current |
| Earth fault | Damaged motor or cable insulation, moisture | Megger motor and cable (disconnected from drive) |
| Motor overload | Load too high, wrong motor data, low speed cooling | Check motor data and load; consider forced cooling |
| Phase loss | Blown fuse, loose connection | Check input and output phases |
Advertisement
Safety
- DC bus capacitors stay charged after isolation; wait the time on the drive label and verify.
- Never megger with the drive connected.
Related Tools, Procedures and Calculators
Frequently Asked Questions
Why does my VFD trip on overvoltage when stopping?
Deceleration is too fast for the load inertia; increase ramp or add braking.
Can I megger through a VFD?
No, disconnect the motor cable from the drive first.
Why do fault codes differ?
Each maker uses its own codes; the causes by fault type are similar.
You May Also Like
Learn more on the blog
How an AC induction motor works
A practical guide on instrumentationblog.in with more background on this equipment.
Read Full ArticleMore Fault Finding Guides
Pressure Transmitter Fault Finding GuidePrintable A4 PDFDP Flow Measurement Fault Finding GuidePrintable A4 PDFMagnetic Flowmeter Fault Finding GuidePrintable A4 PDFCoriolis Flowmeter Fault Finding GuidePrintable A4 PDFVortex and Ultrasonic Flowmeter Fault Finding GuidePrintable A4 PDFRadar and Ultrasonic Level Fault Finding GuidePrintable A4 PDFDP Level and Guided Wave Radar Fault Finding GuidePrintable A4 PDFTemperature Measurement Fault Finding GuidePrintable A4 PDFControl Valve and Positioner Fault Finding GuidePrintable A4 PDFOn Off and ESD Valve Fault Finding GuidePrintable A4 PDFpH and Conductivity Analyser Fault Finding GuidePrintable A4 PDFFixed Gas Detector Fault Finding GuidePrintable A4 PDFPLC Analog Input Fault Finding GuidePrintable A4 PDFModbus and HART Communication Fault Finding GuidePrintable A4 PDFNAMUR NE107 Diagnostic Status GuidePrintable A4 PDF