VFD Fault Finding Guide (Vendor Neutral)

A vendor neutral guide to common variable frequency drive faults by type: causes and checks that apply to most drives. Use your drive manual for exact codes.

One page A4Vendor neutralFree, no sign up

Download

VFD Fault Finding Guide (Vendor Neutral) PDF preview

A one page A4 guide to print for the workshop or keep on your phone in the field. The full content is also shown below.

Download PDF A4 · 51 KB

Before you start

  • Permit, isolation and control room informed.
  • Put the loop in manual or inhibit trips as authorised.
  • Use certified test equipment in hazardous areas.
  • Record as found readings before changing anything.

Quick checks

  • Read the fault code and its history.
  • Isolate and wait for DC bus discharge before touching.
  • Check motor and cable insulation disconnected from the drive.
  • Review ramps and motor parameters.
Advertisement

Symptoms, causes and fixes

SymptomLikely causesChecks and fixes
OvercurrentToo short acceleration, motor or cable short, mechanical jamIncrease ramp; megger motor and cable; check load
Overvoltage (DC bus)Too short deceleration, overhauling load, high supplyIncrease decel; add braking resistor; check supply
UndervoltageSupply dip, loose input, failed rectifier or fuseCheck supply and input terminals
OvertemperatureBlocked fan or filter, high ambient, overloadClean; improve cooling; check current
Earth faultDamaged motor or cable insulation, moistureMegger motor and cable (disconnected from drive)
Motor overloadLoad too high, wrong motor data, low speed coolingCheck motor data and load; consider forced cooling
Phase lossBlown fuse, loose connectionCheck input and output phases
Advertisement

Safety

  • DC bus capacitors stay charged after isolation; wait the time on the drive label and verify.
  • Never megger with the drive connected.

Related Tools, Procedures and Calculators

Frequently Asked Questions

Why does my VFD trip on overvoltage when stopping?

Deceleration is too fast for the load inertia; increase ramp or add braking.

Can I megger through a VFD?

No, disconnect the motor cable from the drive first.

Why do fault codes differ?

Each maker uses its own codes; the causes by fault type are similar.