4 to 20 mA Conversion Table

4 to 20 mA conversion table for loop checks and calibration, with equivalent voltage and pneumatic signals for every 5 % of range.

Excel (.xlsx)Print ready PDF25 rowsFree, no sign up

Download

  • 25 rows of reference data
  • Print ready A4 PDF
  • How to Use sheet with steps
  • Basis and standard stated
  • Excel, Google Sheets and LibreOffice
  • Free, no sign up, no macros

Signal conversion by percent of range

%mA1 to 5 V0 to 10 V3 to 15 psi0.2 to 1.0 bar20 to 100 kPa
04.001.000.003.000.20020.0
54.801.200.503.600.24024.0
105.601.401.004.200.28028.0
156.401.601.504.800.32032.0
207.201.802.005.400.36036.0
258.002.002.506.000.40040.0
308.802.203.006.600.44044.0
359.602.403.507.200.48048.0
4010.402.604.007.800.52052.0
4511.202.804.508.400.56056.0
5012.003.005.009.000.60060.0
5512.803.205.509.600.64064.0
6013.603.406.0010.200.68068.0
6514.403.606.5010.800.72072.0
7015.203.807.0011.400.76076.0
7516.004.007.5012.000.80080.0
8016.804.208.0012.600.84084.0
8517.604.408.5013.200.88088.0
9018.404.609.0013.800.92092.0
9519.204.809.5014.400.96096.0
10020.005.0010.0015.001.000100.0
Advertisement

NAMUR NE 43 signal levels

CurrentMeaning
3.8 to 20.5 mANormal measuring range including under and over range
Below 3.6 mAFailure signal (low)
Above 21.0 mAFailure signal (high)
3.6 to 3.8 and 20.5 to 21.0 mANot used for measurement; treat as suspect

About this Table

4 to 20 mA conversion table for loop checks and calibration, with equivalent voltage and pneumatic signals for every 5 % of range.

Basis: Linear signal scaling: mA = 4 + 16 × % ÷ 100. NAMUR NE 43 for signal limits and failure currents.

How to use

  1. Find the percent of range.
  2. Read the expected mA or other signal.
  3. Engineering value = LRV + % × (URV − LRV) ÷ 100.

Notes

  • 1 to 5 V equals 4 to 20 mA across a 250 Ω resistor.
  • Check the device burnout setting (high or low) before testing alarms.

Related tools

Advertisement

Frequently Asked Questions

What is 50 % in 4 to 20 mA?

12 mA.

What current means a fault?

Below 3.6 mA or above 21 mA to NAMUR NE 43.

Why does the signal start at 4 mA?

A live zero lets the system detect a broken wire and powers 2 wire transmitters.