Square Root Flow and DP Table

Square root flow table for orifice, venturi and other DP flow elements, linking differential pressure, flow and transmitter output.

Excel (.xlsx)Print ready PDF43 rowsFree, no sign up

Download

  • 43 rows of reference data
  • Print ready A4 PDF
  • How to Use sheet with steps
  • Basis and standard stated
  • Excel, Google Sheets and LibreOffice
  • Free, no sign up, no macros

DP percent to flow percent

DP %Flow %Linear DP output mASquare rooted output mA
00.004.0004.000
110.004.1605.600
214.144.3206.263
420.004.6407.200
522.364.8007.578
930.005.4408.800
1031.625.6009.060
1640.006.56010.400
2044.727.20011.155
2550.008.00012.000
3054.778.80012.764
3660.009.76013.600
4063.2510.40014.119
4970.0011.84015.200
5070.7112.00015.314
6077.4613.60016.394
6480.0014.24016.800
7083.6715.20017.387
8089.4416.80018.311
8190.0016.96018.400
9094.8718.40019.179
100100.0020.00020.000
Advertisement

Flow percent to DP percent

Flow %DP %Linear DP output mASquare rooted output mA
00.004.0004.000
50.254.0404.800
101.004.1605.600
152.254.3606.400
204.004.6407.200
256.255.0008.000
309.005.4408.800
3512.255.9609.600
4016.006.56010.400
4520.257.24011.200
5025.008.00012.000
5530.258.84012.800
6036.009.76013.600
6542.2510.76014.400
7049.0011.84015.200
7556.2513.00016.000
8064.0014.24016.800
8572.2515.56017.600
9081.0016.96018.400
9590.2518.44019.200
100100.0020.00020.000

About this Table

Square root flow table for orifice, venturi and other DP flow elements, linking differential pressure, flow and transmitter output.

Basis: Flow is proportional to the square root of differential pressure: Q% = 10 × √(DP%), DP% = Q%² ÷ 100.

How to use

  1. Know whether square root is done in the transmitter or the DCS: only once.
  2. For a linear DP transmitter, use the 'Linear DP output' column.
  3. For a transmitter with square root on, use the 'Square rooted output' column.

Notes

  • Below about 10 % flow (1 % DP) the signal is very sensitive to zero errors; most systems apply low flow cut off.
  • Doubling the flow needs four times the DP.

Related tools

Advertisement

Frequently Asked Questions

What flow is 25 % DP?

50 % flow.

What DP gives 50 % flow?

25 % of the DP range.

Why use low flow cut off?

Near zero, small DP noise gives large flow changes because of the square root.