Full load current in amperes
| hp | kW | 208 V | 230 V | 460 V | 575 V |
|---|---|---|---|---|---|
| 1/2 | 0.37 | 2.4 | 2.2 | 1.1 | 0.9 |
| 3/4 | 0.56 | 3.5 | 3.2 | 1.6 | 1.3 |
| 1 | 0.75 | 4.6 | 4.2 | 2.1 | 1.7 |
| 1 1/2 | 1.12 | 6.6 | 6 | 3 | 2.4 |
| 2 | 1.49 | 7.5 | 6.8 | 3.4 | 2.7 |
| 3 | 2.24 | 10.6 | 9.6 | 4.8 | 3.9 |
| 5 | 3.73 | 16.7 | 15.2 | 7.6 | 6.1 |
| 7 1/2 | 5.59 | 24.2 | 22 | 11 | 9 |
| 10 | 7.46 | 30.8 | 28 | 14 | 11 |
| 15 | 11.19 | 46.2 | 42 | 21 | 17 |
| 20 | 14.91 | 59.4 | 54 | 27 | 22 |
| 25 | 18.64 | 74.8 | 68 | 34 | 27 |
| 30 | 22.37 | 88 | 80 | 40 | 32 |
| 40 | 29.83 | 114 | 104 | 52 | 41 |
| 50 | 37.29 | 143 | 130 | 65 | 52 |
| 60 | 44.74 | 169 | 154 | 77 | 62 |
| 75 | 55.93 | 211 | 192 | 96 | 77 |
| 100 | 74.57 | 273 | 248 | 124 | 99 |
| 125 | 93.21 | 343 | 312 | 156 | 125 |
| 150 | 111.86 | 396 | 360 | 180 | 144 |
| 200 | 149.14 | 528 | 480 | 240 | 192 |
Advertisement
About this Table
Motor full load current table for three phase squirrel cage induction motors, used to size conductors, fuses and overload protection.
Basis: NFPA 70 (NEC) Table 430.250, full load current for three phase induction motors running at usual speeds with normal torque characteristics.
How to use
- Find the motor hp (or nearest kW).
- Read the current at the supply voltage.
- Use the table for conductor and short circuit protection; set overloads from the nameplate.
Notes
- For 220 to 240 V use the 230 V column; 440 to 480 V use 460 V; 550 to 600 V use 575 V.
- IEC motors at 400 to 415 V draw roughly 10 to 15 % more current than the 460 V values; always check the nameplate.
Related tools
Advertisement
Frequently Asked Questions
What is the full load current of a 10 hp motor at 460 V?
14 A from NEC Table 430.250.
Should I use nameplate or table current?
Table current for cables and short circuit protection, nameplate current for overload settings.
Does this apply to single phase motors?
No. Single phase motors use NEC Table 430.248.
You May Also Like
Learn more on the blog
How an AC induction motor works
A practical guide on instrumentationblog.in that explains the engineering behind this table.
Read Full ArticleMore Engineering Reference Tables
Type K Thermocouple Table (mV vs °C)Temperature · Excel and PDFType J Thermocouple Table (mV vs °C)Temperature · Excel and PDFType T Thermocouple Table (mV vs °C)Temperature · Excel and PDFType E Thermocouple Table (mV vs °C)Temperature · Excel and PDFType N Thermocouple Table (mV vs °C)Temperature · Excel and PDFType R Thermocouple Table (mV vs °C)Temperature · Excel and PDFType S Thermocouple Table (mV vs °C)Temperature · Excel and PDFType B Thermocouple Table (mV vs °C)Temperature · Excel and PDFPt100 RTD Table (Ω vs °C)Temperature · Excel and PDFPt1000 RTD Table (Ω vs °C)Temperature · Excel and PDFThermocouple Tolerance Class Table (IEC 60584)Temperature · Excel and PDFRTD Tolerance Class Table (IEC 60751)Temperature · Excel and PDFCarbon Steel Pipe Schedule Chart (ASME B36.10M)Piping · Excel and PDFStainless Steel Pipe Schedule Chart (ASME B36.19M)Piping · Excel and PDFSteel Pipe Weight Chart (kg per metre)Piping · Excel and PDFPipe Inside Diameter and Flow Area ChartPiping · Excel and PDFNPS to DN Pipe Size ChartPiping · Excel and PDFFlange Pressure Temperature Rating Table (ASME B16.5)Piping · Excel and PDFSaturated Steam Table by TemperatureSteam and Water · Excel and PDFSaturated Steam Table by PressureSteam and Water · Excel and PDFSuperheated Steam TableSteam and Water · Excel and PDFWater Density and Viscosity TableSteam and Water · Excel and PDFWater Boiling Point vs Altitude TableSteam and Water · Excel and PDFAWG Wire Size Chart (AWG to mm²)Electrical · Excel and PDFMetric Cable Size and Resistance Table (IEC 60228)Electrical · Excel and PDFIP Rating Chart (IEC 60529)Electrical · Excel and PDFNEMA Enclosure Types Chart (NEMA 250)Electrical · Excel and PDFNEMA to IP Conversion ChartElectrical · Excel and PDFElectrical Wire Colour Code ChartElectrical · Excel and PDF4 to 20 mA Conversion TableInstrumentation · Excel and PDFSquare Root Flow and DP TableInstrumentation · Excel and PDFISA Instrument Letter Codes Table (ISA 5.1)Instrumentation · Excel and PDFHazardous Area Zone and Gas Group TableInstrumentation · Excel and PDFHazardous Area Temperature Class Table (T1 to T6)Instrumentation · Excel and PDFSIL Level PFD and RRF Table (IEC 61508)Instrumentation · Excel and PDFCv to Kv Conversion TableInstrumentation · Excel and PDFNPT Thread Size Chart (ASME B1.20.1)Threads · Excel and PDFBSP Thread Size Chart (ISO 228 and ISO 7)Threads · Excel and PDFMetric Thread Pitch Chart (ISO 261)Threads · Excel and PDF