RTD Tolerance Class Table (IEC 60751)
RTD tolerance table for platinum resistance thermometers, with the limit for each IEC 60751 class at common temperatures in °C and in ohms for a Pt100.
Download
- 19 rows of reference data
- Print ready A4 PDF
- How to Use sheet with steps
- Basis and standard stated
- Excel, Google Sheets and LibreOffice
- Free, no sign up, no macros
Tolerance classes
| Class | Formula (°C) | Wire wound range | Film range |
|---|---|---|---|
| AA | ± (0.10 + 0.0017 |t|) | −50 to 250 °C | 0 to 150 °C |
| A | ± (0.15 + 0.002 |t|) | −100 to 450 °C | −30 to 300 °C |
| B | ± (0.30 + 0.005 |t|) | −196 to 600 °C | −50 to 500 °C |
| C | ± (0.60 + 0.01 |t|) | −196 to 600 °C | −50 to 600 °C |
Tolerance at common temperatures (Pt100)
| °C | AA ± °C | A ± °C | B ± °C | C ± °C | A ± Ω | B ± Ω |
|---|---|---|---|---|---|---|
| −196 | 1.28 | 2.56 | 0.552 | |||
| −100 | 0.35 | 0.80 | 1.60 | 0.142 | 0.324 | |
| −50 | 0.18 | 0.25 | 0.55 | 1.10 | 0.099 | 0.218 |
| 0 | 0.10 | 0.15 | 0.30 | 0.60 | 0.059 | 0.117 |
| 50 | 0.18 | 0.25 | 0.55 | 1.10 | 0.096 | 0.212 |
| 100 | 0.27 | 0.35 | 0.80 | 1.60 | 0.133 | 0.303 |
| 150 | 0.35 | 0.45 | 1.05 | 2.10 | 0.168 | 0.392 |
| 200 | 0.44 | 0.55 | 1.30 | 2.60 | 0.202 | 0.478 |
| 250 | 0.53 | 0.65 | 1.55 | 3.10 | 0.235 | 0.561 |
| 300 | 0.75 | 1.80 | 3.60 | 0.267 | 0.641 | |
| 350 | 0.85 | 2.05 | 4.10 | 0.298 | 0.718 | |
| 400 | 0.95 | 2.30 | 4.60 | 0.327 | 0.793 | |
| 450 | 1.05 | 2.55 | 5.10 | 0.356 | 0.864 | |
| 500 | 2.80 | 5.60 | 0.933 | |||
| 600 | 3.30 | 6.60 | 1.061 |
About this Table
RTD tolerance table for platinum resistance thermometers, with the limit for each IEC 60751 class at common temperatures in °C and in ohms for a Pt100.
Basis: IEC 60751:2008 wire wound element tolerance classes: AA ± (0.1 + 0.0017 |t|), A ± (0.15 + 0.002 |t|), B ± (0.3 + 0.005 |t|), C ± (0.6 + 0.01 |t|) °C, each valid over its stated range.
How to use
- Find the sensor class on its datasheet or tag (A and B are the most common).
- Read the ± °C limit at your temperature, or use the formula for other temperatures.
- For a Pt1000 multiply the Ω values by 10.
Notes
- Values outside a class range are left blank: the class is not defined there.
- Limits shown are for wire wound elements; film elements have narrower ranges (see the first table).
Related tools
Frequently Asked Questions
What is the tolerance of a class A Pt100 at 100 °C?
± 0.35 °C, which is about ± 0.13 Ω.
What does 1/3 DIN mean?
It is a common trade name for class AA, one third of the class B tolerance at 0 °C.
Are film sensors different?
Yes, film elements have narrower valid ranges for each class.