Free engineering calculators and unit convertersceo@instrumentationblog.in
Electrical · Free Excel and PDF

NEMA to IP Conversion Chart

NEMA to IP conversion chart showing the IP rating each NEMA enclosure type meets or exceeds.

Excel (.xlsx)Print ready PDF13 rowsFree, no sign up

Download

  • 13 rows of reference data
  • Print ready A4 PDF
  • How to Use sheet with steps
  • Basis and standard stated
  • Excel, Google Sheets and LibreOffice
  • Free, no sign up, no macros

NEMA type to minimum IP equivalent

NEMA typeMeets or exceeds
1IP10
2IP11
3IP54
3RIP14
3SIP54
4IP66
4XIP66
5IP52
6IP67
6PIP68
12IP52
12KIP52
13IP54
Advertisement

About this Table

NEMA to IP conversion chart showing the IP rating each NEMA enclosure type meets or exceeds.

Basis: NEMA 250 Annex comparison with IEC 60529. The comparison is one way: NEMA type to IP code.

How to use

  1. Find the NEMA type on the enclosure.
  2. Read the IP code it meets or exceeds.
  3. Do not convert IP to NEMA: IP tests do not cover corrosion, icing or gasket ageing.

Notes

  • Hazardous location types 7 to 10 have no IP equivalent.
  • NEMA's own comparison is more conservative for some types (for example IP56 for Type 4 and 4X); many makers test 4X enclosures to IP66.

Related tools

Advertisement

Frequently Asked Questions

What IP is NEMA 4X?

It meets or exceeds IP66.

What IP is NEMA 12?

It meets or exceeds IP54.

Can I use an IP66 box where NEMA 4X is specified?

Not automatically. NEMA 4X also requires corrosion and other tests.