Control Valve Calibration Report (Positioner Stroke Check) Template

A stroke check record for control valves with positioners. Enter the measured travel at each signal; the sheet converts it to % open, calculates the position error and checks the tolerance.

Excel (.xlsx)Printable PDFFilled exampleFree, no sign up

Download

  • How to Use sheet with steps
  • Template sheet, blank and ready
  • Example sheet, filled in
  • 112 built in formulas
  • A4 landscape print setup
  • Works in Excel, Google Sheets and LibreOffice

Preview of the Filled Example

This is the Example sheet from the download, so you can see exactly how the completed control valve calibration report (positioner stroke check) looks.

Tag numberFV 3101
ServiceFeed flow to column C 301
Valve type and sizeGlobe, 3", 300#
Actuator actionAir to open (fail close)
Positioner make and modelFisher DVC6200
Positioner serial noDVC 551029
Rated travel (mm)40
Position tolerance (± % travel)1
Air supply (bar)4
Test date12 Oct 2026
Full stroke time, opening (s)6.5
Full stroke time, closing (s)5.8
Fail action on air loss correct?Yes
Position feedback to DCS correct?Yes
Air leaks checked?Yes
Tight shut off at 0 %?Yes

Stroke check (direct acting: 4 mA closed, 20 mA open)

Signal (%)Signal (mA)As found travel (mm)As found position (%)As found error (%)As left travel (mm)As left position (%)As left error (%)Result
04.000.00.00.00.00.00.0PASS
258.0010.927.22.210.025.00.0PASS
5012.0020.852.02.020.150.20.3PASS
7516.0030.776.81.830.075.00.0PASS
10020.0039.498.5−1.540.0100.00.0PASS
7516.0030.977.22.230.175.20.2PASS
5012.0021.152.82.820.150.20.3PASS
258.0011.228.03.010.125.20.2PASS
04.000.30.80.80.00.00.0PASS
Maximum as left error (%):0.3  ·  Overall result:PASS
Advertisement

About the Control Valve Calibration Report (Positioner Stroke Check)

A control valve that does not go where the controller tells it to causes poor control, oscillation and energy loss. This report checks that the valve position follows the 4 to 20 mA signal across the full stroke, upscale and downscale, which also shows friction and dead band in the valve and actuator.

How to fill in this template

  1. Enter the rated travel from the valve nameplate and the allowed position tolerance.
  2. With the process isolated and the valve safe to stroke, inject each signal with a mA source or from the DCS.
  3. Measure the stem travel with a scale or dial gauge (or read the positioner travel) and type it in As found travel (mm).
  4. If errors exceed tolerance, run the positioner auto calibration or adjust zero and span, then record As left travel.
  5. Time a full open and close stroke and complete the functional checks before returning the valve to service.

What the formulas do

  • Signal (mA) = 4 + 16 × signal % ÷ 100.
  • Position (%) = measured travel ÷ rated travel × 100.
  • Error (%) = position % − signal %. PASS when within tolerance (as left values used when present).

Related tools

Advertisement

Frequently Asked Questions

How often should control valves be stroke checked?

At every turnaround and after any positioner or actuator work, and more often for critical loops.

What tolerance is typical for a control valve stroke check?

± 1 % of travel is common with modern digital positioners; ± 2 % for older pneumatic positioners.

What causes a difference between upscale and downscale positions?

Packing friction and dead band. A large difference points to tight packing, a sticking stem or positioner problems.