Pressure Switch Calibration Report Template

Record the trip and reset pressure of a switch over three trials. The sheet calculates the deadband, the deviation from set point and the repeatability, and marks the switch pass or fail.

Excel (.xlsx)Printable PDFFilled exampleFree, no sign up

Download

  • How to Use sheet with steps
  • Template sheet, blank and ready
  • Example sheet, filled in
  • 36 built in formulas
  • A4 landscape print setup
  • Works in Excel, Google Sheets and LibreOffice

Preview of the Filled Example

This is the Example sheet from the download, so you can see exactly how the completed pressure switch calibration report looks.

Tag numberPSH 1105
ServiceAir receiver high pressure
Make and modelDanfoss KPS 35
Serial numberKPS 60113
Adjustable range0 to 16 bar
Unitbar
Set point8
Trip onRising
Set point tolerance (±)0.1
Contact usedNO, opens on trip
Pressure standardDruck DPI 620
Standard certificate noNABL/CC 24118
Calibration date12 Oct 2026
Work order noWO 26 0433

Trip and reset test

TrialAs found tripAs found resetAs found deadbandAs found deviation from SPAs left tripAs left resetAs left deadbandAs left deviation from SPResult
18.257.620.630.258.037.550.480.03PASS
28.227.600.620.228.017.530.480.01PASS
38.277.630.640.278.027.560.460.02PASS
As left repeatability (max − min trip):0.02  ·  As left average deadband:0.47  ·  Overall result:PASS
Advertisement

About the Pressure Switch Calibration Report

Pressure switches protect equipment and people, so their trip point must be proven regularly. Unlike a transmitter, a switch has a trip value and a reset value, and the difference (deadband) matters as much as the set point. Three trials reveal poor repeatability caused by worn diaphragms or sticky mechanisms.

How to fill in this template

  1. Enter the set point, trip direction and allowed tolerance from the instrument data sheet or alarm and trip list.
  2. Connect a continuity tester or multimeter across the contact used in the circuit.
  3. Raise the pressure slowly near the set point and record the trip value; lower it until the contact resets and record the reset value. Repeat three times.
  4. If the trip is out of tolerance, adjust the range screw and record three as left trials.
  5. Check repeatability and deadband, then sign the report.

What the formulas do

  • Deadband = |trip − reset|.
  • Deviation = trip − set point.
  • Result uses as left values when present, otherwise as found; PASS when |deviation| ≤ tolerance.
  • Repeatability = highest trip − lowest trip over the trials.

Related tools

Advertisement

Frequently Asked Questions

What is deadband in a pressure switch?

The difference between the trip and reset pressures. Too small causes chattering; too large delays the reset.

Why test three trials?

To check repeatability. A switch that trips at a different value each time cannot be trusted for protection.

How slowly should pressure be applied?

Slowly enough that the reading on the standard is stable at the moment the contact changes, typically a few % of span per minute near the set point.