Free engineering calculators and unit convertersceo@instrumentationblog.in
Engineering Documents · Free Template

Instrument Air Header and Take Off Schedule Template

List every instrument air consumer by header and take off valve, with steady consumption. The sheet totals air use and adds a design margin to size headers and compressors.

Excel (.xlsx)Printable PDFFilled exampleFree, no sign up

Download

  • How to Use sheet with steps
  • Template sheet, blank and ready
  • Example sheet, filled in
  • 6 built in formulas
  • A4 landscape print setup
  • Works in Excel, Google Sheets and LibreOffice

Preview of the Filled Example

This is the Example sheet from the download, so you can see exactly how the completed instrument air header and take off schedule looks.

AreaArea 300
Header pressure (bar g)7
Design margin (%)30
RevisionA

Take offs

NoHeaderTake offInstrument tagConsumerTypeSteady use (Nm³/h)Valve sizeTube sizeStatusRemarks
1IAH 301TO 01FV 3101Feed control valvePositioner0.601/2"10 mmUsed
2IAH 301TO 02XV 3102Shutdown valveOn off actuator0.101/2"10 mmUsed
3IAH 301TO 03AT 3103Analyser purgePurge1.501/2"10 mmUsed
4IAH 301TO 04SpareSpare0.001/2"Spare
Total steady use (Nm³/h):2.20  ·  Design use with margin (Nm³/h):2.86  ·  Spare take offs:1
Advertisement

About the Instrument Air Header and Take Off Schedule

An air header schedule keeps instrument air distribution organised: every consumer has a take off, spares are visible, and total demand is known for sizing headers, dryers and compressors.

How to fill in this template

  1. List each header and its take off valves.
  2. Assign consumers and their steady air use from vendor data.
  3. Mark spare take offs.
  4. Read the total and design use with margin.
  5. Use totals to check header size and compressor capacity.

What the formulas do

  • Total = sum of steady consumption.
  • Design use = total × (1 + margin).

Related tools

Advertisement

Frequently Asked Questions

What steady consumption does a positioner have?

Typically a fraction of a Nm³/h; use vendor data, since it varies widely.

Should transient demand be included?

Size separately for valves that stroke together, such as shutdown groups.

How many spares?

Commonly about 20 % per header.