DP Transmitter Calibration Report Template

A 5 point calibration report for differential pressure transmitters in flow, level and filter service, with a zero check at line pressure and square root output support.

Excel (.xlsx)Printable PDFFilled exampleFree, no sign up

Download

  • How to Use sheet with steps
  • Template sheet, blank and ready
  • Example sheet, filled in
  • 116 built in formulas
  • A4 landscape print setup
  • Works in Excel, Google Sheets and LibreOffice

Preview of the Filled Example

This is the Example sheet from the download, so you can see exactly how the completed dp transmitter calibration report looks.

Tag numberFT 3105
ServiceFeed water flow
Make and modelVendor DP transmitter
Serial numberDP 220781
Calibrated range LRV (mbar)0
Calibrated range URV (mbar)250
Output functionLinear (square root in DCS)
Static pressure in service (bar g)16
Tolerance (± % of span)0.25
Manifold3 valve
Zero at atmosphere (mA)4.002
Zero at line pressure, equaliser open (mA)4.018
Static pressure zero shift (% span)0.10
Pressure standardLow range pressure module 0 to 1 bar
Standard certificate noCC 24502
Calibration date25 Oct 2026

Calibration results (5 point, upscale and downscale)

Test point (% of span)Applied DP (mbar)Expected output (mA)As found output (mA)As found error (% span)As found resultAs left output (mA)As left error (% span)As left result
00.004.0004.0180.11PASS4.0020.01PASS
2562.508.0008.0460.29FAIL8.0030.02PASS
50125.0012.00012.0610.38FAIL12.0010.01PASS
75187.5016.00016.0820.51FAIL16.0020.01PASS
100250.0020.00020.0900.56FAIL20.0010.01PASS
75187.5016.00016.0770.48FAIL16.0030.02PASS
50125.0012.00012.0560.35FAIL12.0020.01PASS
2562.508.0008.0400.25PASS8.0020.01PASS
00.004.0004.0160.10PASS4.0010.01PASS
Maximum as found error (% span):0.56  ·  Maximum as left error (% span):0.02  ·  Overall result (as left if adjusted, else as found):PASS
Advertisement

About the DP Transmitter Calibration Report

DP transmitters measure small pressure differences at high line pressure. Besides the usual 5 point test, a zero check at line pressure reveals the static pressure effect, which can be a large error at low ranges.

How to fill in this template

  1. Enter tag, range in mbar and tolerance.
  2. With the transmitter in service, close HP and LP valves, open the equaliser and record the zero at line pressure; then vent and record the zero at atmosphere.
  3. Isolate, connect the pressure standard to the HP side and vent the LP side.
  4. Apply each test point upscale and downscale and record the as found output.
  5. Trim zero and span if any point fails, record as left values, and return the manifold to service in the correct sequence.

What the formulas do

  • Applied DP = LRV + span × test point %.
  • Expected output = 4 + 16 × test point % mA.
  • Error (% span) = (measured − expected) ÷ 16 × 100.
  • Static pressure zero shift = (zero at line pressure − zero at atmosphere) ÷ 16 × 100.

Related tools

Advertisement

Frequently Asked Questions

Why check zero at line pressure?

Line pressure deforms the sensor and shifts the zero. Trimming zero at line pressure removes this offset.

Should I calibrate in square root mode?

Calibrating in linear mode is simpler; if square root is used, compare against the square root expected current.

Which side gets the pressure?

The HP side, with the LP side open to atmosphere.