Maintenance · Free Template

Pressure Relief Valve Bench Test Record Template

Record bench tests of pressure relief valves: as found and as left pop pressure against the set pressure with an automatic tolerance check, seat tightness and reseat pressure, and the next test date.

Excel (.xlsx)Printable PDFFilled exampleFree, no sign up

Download

  • How to Use sheet with steps
  • Template sheet, blank and ready
  • Example sheet, filled in
  • 156 built in formulas
  • A4 landscape print setup
  • Works in Excel, Google Sheets and LibreOffice

Preview of the Filled Example

This is the Example sheet from the download, so you can see exactly how the completed pressure relief valve bench test record looks.

Site / unitUtilities
Test bench / gaugeTB 02, gauge cal. 2026 08
Test mediumAir / nitrogen
Test interval (months)36

Relief valves tested (pressures in bar g)

TagServiceSizeSet pressureAs found popAs found resultAs left popAs left resultReseatSeat tight?Test dateNext dueTested byRemarks
PSV 1001Air receiver1" x 2"10.0010.18PASS10.05PASS9.30Yes20 Oct 202620 Oct 2029Tech A
PSV 2102Steam header2" x 3"16.0016.90FAIL16.10PASS15.00Yes20 Oct 202620 Oct 2029Tech AAs found high; spring adjusted
PSV 3103Pump discharge3/4" x 1"4.004.08PASS4.05PASS3.70Yes21 Oct 202621 Oct 2029Tech B
Valves tested:3  ·  As found failures:1  ·  As left failures:0
Advertisement

About the Pressure Relief Valve Bench Test Record

Relief valves are tested at intervals to prove they lift at their set pressure and reseat tightly. The as found result matters most: it shows whether the valve would have protected the equipment since the last test, and drives the test interval.

How to fill in this template

  1. Enter the test bench, medium and test interval.
  2. For each valve record the set pressure from the nameplate and the as found pop pressure before any adjustment.
  3. Adjust if needed and record the as left pop and reseat pressure, and whether the seat is tight.
  4. Results show PASS or FAIL against the tolerance; the next due date follows from the interval.
  5. As found failures should be reported: they show the valve would not have protected the equipment as intended.

What the formulas do

  • Tolerance = ± 0.138 bar for set ≤ 4.83 bar g, otherwise ± 3 % of set.
  • Result = PASS if |pop − set| ≤ tolerance.
  • Next due = test date + interval.

Related tools

Advertisement

Frequently Asked Questions

What is the set pressure tolerance of a relief valve?

Under ASME Section VIII, ± 2 psi up to 70 psi set pressure and ± 3 % above. Other codes may differ.

Why record the as found pop pressure?

It shows how the valve performed in service. A high as found result means the equipment was less protected than designed.

What is reseat pressure?

The pressure at which the valve closes again after lifting; it is lower than the set pressure by the blowdown.

You May Also Like

Learn more on the blog

Pressure switch calibration steps

A practical guide on instrumentationblog.in that explains the procedure behind this template and how engineers apply it on real plants.

Read Full Article

More Maintenance Templates

All Templates and Downloads