On Off (Shutdown) Valve Data Sheet Template
A data sheet for automated on off and emergency shutdown valves: process and shut off conditions, valve and seat details, actuator sizing basis, fail action, stroke time and accessories.
Download
- How to Use sheet with steps
- Template sheet, blank and ready
- Example sheet, filled in
- Drop down lists for consistent entries
- A4 portrait print setup
- Works in Excel, Google Sheets and LibreOffice
Preview of the Filled Example
This is the Example sheet from the download, so you can see exactly how the completed on off (shutdown) valve data sheet looks.
Specification
| No | Parameter | Value | Unit / notes |
|---|---|---|---|
| General | |||
| 1 | Tag number | XV 4101 | |
| 2 | Service / function | Tank outlet shutdown | |
| 3 | Line number / size | 6" / Sch 40 | |
| 4 | P&ID number | PID 400 01 | |
| 5 | SIL requirement | SIL 2 | |
| Process conditions | |||
| 6 | Fluid | Diesel | |
| 7 | Operating pressure / temperature | 3 / 40 | bar g / °C |
| 8 | Design pressure / temperature | 10 / 80 | bar g / °C |
| 9 | Maximum shut off pressure | 10 | bar |
| 10 | Flow at normal operation | 120 | m³/h |
… and 23 more rows in the download.
About the On Off (Shutdown) Valve Data Sheet
Shutdown valves must close tightly and quickly when demanded, often after years without moving. A data sheet that fixes shut off pressure, leakage class, fail action and stroke time gives the vendor what is needed to size the actuator and accessories correctly.
How to fill in this template
- Enter the function and SIL requirement from the cause and effect matrix or SRS.
- Give the maximum shut off pressure; it sets the actuator torque.
- Specify seat leakage, fire safe and antistatic requirements.
- Define fail action, air supply range and required stroke times.
- List accessories: solenoid, limit switches, partial stroke test device and quick exhaust.
What the formulas do
- No formulas: specification document laid out in sections like an ISA 20 style data sheet.
Related tools
Frequently Asked Questions
What is shut off pressure?
The maximum pressure difference the valve must close against and seal. It sets the actuator torque.
What does fire safe mean?
The valve still seals within allowed leakage after a fire test, for example to API 607.
Why specify stroke time?
The safety function needs the valve closed within the process safety time; slow actuators or small solenoids can make it miss.
Learn more on the blog
What is SIL (safety integrity level)
A practical guide on instrumentationblog.in that explains the procedure behind this template and how engineers apply it on real plants.