Instrument Junction Box Data Sheet Template

A data sheet for field instrument junction boxes, covering enclosure, protection ratings, terminals, earthing and gland entries.

Excel (.xlsx)Printable PDFFilled exampleFree, no sign up

Download

  • How to Use sheet with steps
  • Template sheet, blank and ready
  • Example sheet, filled in
  • Drop down lists for consistent entries
  • A4 portrait print setup
  • Works in Excel, Google Sheets and LibreOffice

Preview of the Filled Example

This is the Example sheet from the download, so you can see exactly how the completed instrument junction box data sheet looks.

ProjectBoiler 3 upgrade
RevisionA
Date24 Oct 2026
Requisition noREQ INST 038

Specification

NoParameterValueUnit / notes
General
1Tag numberJB 2001
2Area / locationArea 200, pipe rack
3Hazardous areaZone 2, IIB T4
4Signal type (analog, digital, IS, fieldbus)Analog 4 to 20 mA, non IS
Enclosure
5MaterialSS 316L
6Size (H x W x D)400 x 300 x 200mm
7Ingress protectionIP66
8Ex protectionEx eb IIC T6 Gb
9MountingWall / stand
10Door / coverHinged, padlockable

… and 13 more rows in the download.

Advertisement

About the Instrument Junction Box Data Sheet

Junction boxes collect field cables into multicores. A clear data sheet prevents wrong Ex ratings, too few terminals and missing earth bars.

How to fill in this template

  1. Define location, area classification and signal type.
  2. Choose enclosure material, size, IP and Ex protection.
  3. Count terminals including spares and earth requirements.
  4. List gland entries by cable size.
  5. Add labelling and test requirements.

What the formulas do

  • No formulas: specification document laid out in sections like an ISA 20 style data sheet.

Related tools

Advertisement

Frequently Asked Questions

Why separate IS and non IS?

IEC 60079-14 requires separation so energy cannot pass into IS circuits.

How many spare terminals?

Commonly about 20 %; follow your project specification.

Ex e or Ex d junction box?

Ex e (increased safety) is common for terminals; Ex d is used when devices inside can spark.