Pressure Transmitter Data Sheet Template
A specification data sheet for pressure transmitters, laid out in the familiar ISA style: general, process conditions, transmitter specification, accessories and purchase details.
Download
- How to Use sheet with steps
- Template sheet, blank and ready
- Example sheet, filled in
- Drop down lists for consistent entries
- A4 portrait print setup
- Works in Excel, Google Sheets and LibreOffice
Preview of the Filled Example
This is the Example sheet from the download, so you can see exactly how the completed pressure transmitter data sheet looks.
Specification
| No | Parameter | Value | Unit / notes |
|---|---|---|---|
| General | |||
| 1 | Tag number | PT 1101 | |
| 2 | Service | Steam header pressure | |
| 3 | Line / equipment number | 8" ST 1101 | |
| 4 | P&ID number | PID 100 02 | |
| 5 | Hazardous area classification | Zone 2, IIB T3 | IEC 60079-10-1 |
| Process conditions | |||
| 6 | Fluid | Saturated steam | |
| 7 | Operating pressure (normal / max) | 10 / 12 | bar g |
| 8 | Design pressure | 16 | bar g |
| 9 | Operating temperature (normal / max) | 184 / 192 | °C |
| 10 | Design temperature | 220 | °C |
… and 21 more rows in the download.
About the Pressure Transmitter Data Sheet
The instrument data sheet is the contract between the engineer and the vendor: it defines exactly what must be supplied. A complete pressure transmitter data sheet prevents wrong ranges, wrong materials and wrong Ex certificates, the three most common reasons a transmitter is rejected at receipt.
How to fill in this template
- Fill the general and process sections from the process data sheet and P&ID; always give normal, maximum and design values.
- Choose a measuring range so the calibrated range sits comfortably inside it, typically 1:1 to 10:1 turndown.
- Specify the Ex certification to match the hazardous area classification.
- Select wetted materials for the process fluid (SS 316L for most services, Hastelloy C or tantalum for corrosive fluids).
- Issue the data sheet with the requisition; the vendor completes the make and model.
What the formulas do
- No formulas: specification document. Section rows organise the data like an ISA 20 style data sheet.
Related tools
Frequently Asked Questions
What is an instrument data sheet?
A document that specifies the process conditions and the required features of one instrument (or a group of identical instruments) for purchase.
What is the difference between measuring range and calibrated range?
The measuring range is what the sensor can handle; the calibrated range is the part of it scaled to 4 to 20 mA for this service.
Why add a siphon for steam?
A siphon (pigtail) holds condensate that protects the transmitter diaphragm from live steam temperature.