Flow Meter / Transmitter Data Sheet Template
A specification data sheet for flow meters and transmitters: magnetic, vortex, Coriolis, ultrasonic or DP. It covers process conditions, meter and transmitter details and a quick turndown check.
Download
- How to Use sheet with steps
- Template sheet, blank and ready
- Example sheet, filled in
- 2 built in formulas
- A4 portrait print setup
- Works in Excel, Google Sheets and LibreOffice
Preview of the Filled Example
This is the Example sheet from the download, so you can see exactly how the completed flow meter / transmitter data sheet looks.
Specification
| No | Parameter | Value | Unit / notes |
|---|---|---|---|
| General | |||
| 1 | Tag number | FT 3101 | |
| 2 | Service | Cooling water to E 301 | |
| 3 | Line number / size / schedule | 6" / Sch 40 | |
| 4 | P&ID number | PID 300 02 | |
| 5 | Hazardous area | Safe area | |
| Process conditions | |||
| 6 | Fluid / phase | Cooling water, liquid | |
| 7 | Flow rate (normal / maximum) | 110 / 140 | m³/h |
| 8 | Minimum flow | 40 | m³/h |
| 9 | Operating pressure (normal / maximum) | 4 / 6 | bar g |
| 10 | Operating temperature (normal / maximum) | 32 / 45 | °C |
… and 24 more rows in the download.
About the Flow Meter / Transmitter Data Sheet
Flow meter selection depends on the fluid as much as on the flow: a magnetic meter needs a conductive liquid, a vortex meter needs enough velocity, and a Coriolis meter needs an acceptable pressure drop. A complete data sheet with minimum, normal and maximum conditions lets the vendor size the meter properly.
How to fill in this template
- Give minimum, normal and maximum flow and the operating and design conditions from the process data sheet.
- Add fluid properties the meter type needs: conductivity for magnetic meters, viscosity and density for vortex and DP meters.
- Select the meter type, size and calibrated range; the turndown row shows how far the minimum flow is below full scale.
- Specify materials, output, Ex certification and enclosure.
- Issue with the requisition; the vendor completes the model and sizing.
What the formulas do
- Turndown = calibrated range maximum ÷ minimum flow.
Related tools
Frequently Asked Questions
What process data does a flow meter data sheet need?
Fluid and phase, minimum, normal and maximum flow, pressure and temperature, density, viscosity, and for magnetic meters, conductivity.
Why give minimum flow?
It sets the turndown the meter must handle. Many meters lose accuracy or cut off at low flow.
Should the meter be line size?
Not always. Vortex and magnetic meters are often one size smaller than the line to raise velocity; check the sizing with the vendor.
Learn more on the blog
Types of flow meters
A practical guide on instrumentationblog.in that explains the procedure behind this template and how engineers apply it on real plants.