HART Transmitter Configuration Record Template

Record every HART parameter before and after you touch a transmitter. The sheet flags every changed parameter so range or damping changes never go unnoticed.

Excel (.xlsx)Printable PDFFilled exampleFree, no sign up

Download

  • How to Use sheet with steps
  • Template sheet, blank and ready
  • Example sheet, filled in
  • 46 built in formulas
  • A4 portrait print setup
  • Works in Excel, Google Sheets and LibreOffice

Preview of the Filled Example

This is the Example sheet from the download, so you can see exactly how the completed hart transmitter configuration record looks.

Tag numberFT 3101 (DP flow)
Configuration toolHART communicator / AMS
Date12 Oct 2026
MOC / work orderMOC 26 041

Configuration parameters

NoParameterAs foundAs leftChange
Identification
1TagFT3101FT3101
2Long tagFT 3101 FEED FLOWFT 3101 FEED FLOW
3DescriptorFEED TO C301FEED TO C301
4MessageRANGE CHG MOC 26 041CHANGED
5Date15/03/202412/10/2026CHANGED
6Polling address00
Measurement
7Primary variable unitmbarmbar
8Lower range value (LRV)00
9Upper range value (URV)250320CHANGED
10Transfer functionSquare rootSquare root

… and 14 more rows in the download.

Parameters changed:5
Advertisement

About the HART Transmitter Configuration Record

Smart transmitters hold their range, units, damping and alarm settings in memory, invisible from the outside. A configuration record captures that hidden state before and after any intervention, which protects you when a reading looks wrong after maintenance and is required for SIS devices under IEC 61511.

How to fill in this template

  1. Connect the HART communicator and record every parameter in As found before changing anything.
  2. Make the approved changes and record the As left values.
  3. The Change column marks every parameter that differs; check that only approved items show CHANGED.
  4. Update the DCS range, instrument index and data sheet if the range or units changed.
  5. Sign and file with the MOC or work order.

What the formulas do

  • Change shows CHANGED when the as found and as left text differ (EXACT comparison).
  • Parameters changed = count of CHANGED.

Related tools

Advertisement

Frequently Asked Questions

Why record HART configuration?

Because range, damping or alarm direction can be changed from a handheld without any visible sign. A record proves what was set and when.

What is NAMUR NE 43?

A recommendation that defines failure signal levels: below 3.6 mA or above 21 mA, with normal saturation at 3.8 and 20.5 mA.

Should write protect be on?

For SIS and critical transmitters, yes, to prevent unauthorised changes.